Permit 202006048153
950 Tennessee St
revision to pa# 2017-1201-5291 s3 fire sprinkler addendum.ductile iron piping acceptable for use for underground main piping can have a mechanical joint with mege-lugs in lieu of thrust blocks minimum pipe bury to be 24".
- Outcome
- Completed (city status: complete, Jan 14, 2021)
- Filed
- Jun 4, 2020
- Permit issued
- Jul 16, 2020
- Final sign-off
- Jan 14, 2021
- Declared cost
- $3,000
- Building use
- apartments
- Neighborhood
- Potrero Hill
- Contractor
- Thompson Builders Corp (license 626859)
- Property
- All permits at this address (block 4107, lot 001B)